As default the parameter is set to 10 seconds, this is fine for when the load is low, but as soon as the load increases, the system will have difficulty transferring the load within the timespan.
So a solution, would be to change the parameter timer on parameter 2631. From 10 Sec to 60 Sec. Then the issues should be gone.
This can be done in 2 ways you can do it from the USW-3 or you can do it from the Display unit.
Here is how you change it form the Display Unit:
- Hit the Jump menu and navigate to parameter #2631.
- Enter the Password Standard it is set to: 2000.
- Make adjustment to the parameter and save it.
- Now see that the change is made, and you are done.